What cable types are included in the TIA 568 structured cabling standards?

We can supply all the products you need for structured cabling. It's cover network cable,patch cord,patch panels,optical fiber and cabinet accessories.If you are interested in it, please contact me.

What is a structured cabling system?

As wiring and connection points evolved, more standardization was needed for cabling, connectors and the different types of wiring, including copper, fiber and coaxial. The American National Standards Institute and Telecommunications Industry Association set forth a series of standards, ANSI/TIA-568, to introduce guidelines for all aspects of residential and commercial building cable distribution systems.

These standards shape the structured cabling system. Structured cabling is based on six components that, together, provide a convenient, repeatable and easily implemented framework for installing telecommunications cabling. The six components of structured cabling are the following:

  1. Entrance Facilities
  2. Equipment Room
  3. Backbone Cabling
  4. Telecommunications Room
  5. Horizontal Cabling
  6. Work Area

Why is structured cabling important?

Structured cabling greatly simplifies the installation of a cable infrastructure that supports a wide variety of voice and data communications equipment. Whether installing a coaxial outlet in a home or wiring a skyscraper, the components are all made to specific standards for electrical transmission, resistance, cable lengths, connectors and cable fabrication.

Structured cabling also enhances trouble shooting of wiring problems when using the proper diagnostic equipment, which is designed to be compatible with the ANSI/TIA-568.0/1 standards. Installation is also easier with structured cabling because the interfaces are standardized, typically using snap-in connectors.

Structured cabling standards

The development of structured cabling systems was greatly helped with the release of the ANSI/TIA-568 standard in 1991. Its sections included Generic Telecommunications Cabling for Customer Premises (C.0) and Commercial Building Telecommunications Infrastructure Standard (C.1). The two standards have been updated numerous times in the past 30 years, and the current iterations are ANSI/TIA-568.0 (customer premises) and ANSI/TIA-568.1 (commercial buildings). Both were most recently updated in March 2020.

Structured cabling benefits

The installation, troubleshooting and maintenance of cable infrastructures are greatly simplified with structured cabling. This saves money through standardization of all hardware components and cable types. It also saves time with installation as connectors and their wiring are greatly simplified. The ANSI/TIA-568 standard is adaptable to virtually any kind of residential and commercial wiring requirements.

Note: Many topics at this site are reduced versions of the text in "The Encyclopedia of Networking and Telecommunications." Search results will not be as extensive as a search of the book's CD-ROM.

In the mid-1980s, the TIA (Telecommunications Industry Association) and the EIA (Electronic Industries Association) began developing methods for cabling buildings, with the intent of developing a uniform wiring system that would support multivendor products and environments. In 1991, the TIA/EIA released the TIA/EIA 568 Commercial Building Telecommunication Cabling standard. Note that the ISO/IEC-11801 Generic Customer Premises Cabling standard is an international cabling standard that is based on the ANSI/TIA/EIA-568 cabling standard.

The TIA/EIA structured cabling standards define how to design, build, and manage a cabling system that is structured, meaning that the system is designed in blocks that have very specific performance characteristics. The blocks are integrated in a hierarchical manner to create a unified communication system. For example, workgroup LANs represent a block with lower-performance requirements than the backbone network block, which requires high-performance fiber-optic cable in most cases. The standard defines the use of fiber-optic cable (single and multimode), STP (shielded twisted pair) cable, and UTP (unshielded twisted pair) cable.

The initial TIA/EIA 568 document was followed by several updates and addendums as outlined below. A major standard update was released in 2000 that incorporates previous changes.

  • TIA/EIA-568-A-1995 (Commercial Building Telecommunications Wiring Standards)
  •     Defines a standard for building cable system for commercial buildings that support data networks, voice, and video. It also defines the technical and performance criteria for cabling.
  • TIA/EIA-568-A updates (1998-1999)
  •     The TIA/EIA-568 was updated several times through this time period. Update A1 outlined propagation delay and delay skew parameters. Update A2 specified miscellaneous changes. Update A3 specified requirements for bundled and hybrid cables. Update A4 defined NEXT and return loss requirements for patch cables. Finally, update A5 defined performance requirements for Enhanced Category 5 (Category 5E).
  • TIA 568-B.1-2000 (Commercial Building Telecommunications Wiring Standard)
  •     The year 2000 update packages all the previous addendums and service updates into a new release and, most important, specifies that Category 5E cable is the preferred cable type that can provide minimum acceptable performance levels. Several addendums were also released that specify technical information for 100-ohm twisted-pair cable, shielded twisted-pair cable, and optical fiber cable.
  • TIA/EIA-569-A-1995 (Commercial Building Standard for Telecommunications Pathways and Spaces)   
  • This standard defines how to build the pathways and spaces for telecommunication media.
  • TIA 570-A-1998 (Residential and Light Commercial Telecommunications Wiring Standard)
  •     This standard specifies residential cabling.
  • TIA/EIA-606-1994 (Building Infrastructure Administration Standard)
  •     This standard defines the design guidelines for managing a telecommunications infrastructure.
  • TIA/EIA-607-1995 (Grounding and Bonding Requirements)
  •     This standard defines grounding and bonding requirements for telecommunications cabling and equipment.

The current trend is to evolve the standards to support high-speed networking such as Gigabit Ethernet and define advanced cable types and connectors such as four-pair Category 6 and Category 7 cable. Category 6 is rated for channel performance up to 200 MHz, while Category 7 is rated up to 600 MHz. See "Cable and Wiring" for more information about cable types.

The remainder of this section discusses the TIA/EIA-568 standard in general, rather than any specific release. According to TIA/EIA 568 documents, the wiring standard is designed to provide the following features and functions:

  • A generic telecommunication wiring system for commercial buildings

  • Defined media, topology, termination and connection points, and administration

  • Support for multiproduct, multivendor environments

  • Direction for future design of telecommunication products for commercial enterprises

  • The ability to plan and install the telecommunication wiring for a commercial building without any prior knowledge of the products that will use the wiring

The layout of a TIA/EIA 568-A structured cable system is illustrated in Figure T-8. The hierarchical structure is apparent in the multifloor office building. A vertical backbone cable runs from the central hub/switch in the main equipment room to a hub/switch in the telecommunication closet on each floor. Work areas are then individually cabled to the equipment in the telecommunication closet. The logical hierarchy is illustrated in Figure T-9.

Figure T-8 (see book, page 1248)

Figure T-9 (see book, page 1249)

The TIA standard defines the parameters for each part of the cabling system, which includes work area wiring, horizontal wiring, telecommunication closets, equipment rooms and cross- connects, backbone (vertical) wiring, and entrance facilities. Each of these is described next. Additional details, specifications, and illustrations are available at the Siemon's Web site listed on the related entries page.

Work Area

The work area wiring subsystem consists of the communication outlets (wallboxes and faceplates), wiring, and connectors needed to connect the work area equipment (computers, printers, and so on) via the horizontal wiring subsystem to the telecommunication closet. The standard requires that two outlets be provided at each wall plate-one for voice and one for data.

Horizontal Wiring

The horizontal wiring system runs from each workstation outlet to the telecommunication closet. The maximum horizontal distance from the telecommunication closet to the communication outlets is 90 meters (295 feet) independent of media type. An additional 6 meters (20 feet) is allowed for patch cables at the telecommunication closet and at the workstation, but the combined length cannot exceed 10 meters (33 feet). As mentioned earlier, the work area must provide two outlets. The horizontal cable should be four-pair 100-ohm UTP cable (the latest standards specify Category 5E), two-fiber 62.5/125-mm fiber-optic cable, or multimode 50/125-mm multimode fiber-optic cable. Coaxial cable is no longer recommended.

Telecommunication Closet

The telecommunication closet contains the connection equipment for workstations in the immediate area and a cross-connection to an equipment room. The telecommunication closet is a general facility that can provide horizontal wiring connections, as well as entrance facility connections. There is no limit on the number of telecommunication closets allowed. Some floors in multistory office buildings may have multiple telecommunication closets, depending on the floor plan. These may be connected to an equipment room on the same floor.

Equiptment Rooms and Main Cross-Connects

An equipment room provides a termination point for backbone cabling that is connected to one or more telecommunication closets. It may also be the main cross-connection point for the entire facility. In a campus environment, each building may have its own equipment room, to which telecommunication closet equipment is connected, and the equipment in this room may then be connected to a central campus facility that provides the main cross-connect for the entire campus.

Backbone Wiring

The backbone wiring runs up through the floors of the building (risers) or across a campus and provides the interconnection for equipment rooms and telecommunication closets. The distance limitations of this cabling depend on the type of cable and facilities it connects. Refer to Figure T-11 and the following table. Note that UTP is limited to 90 meters.

Cable Type

MC to ER

Multimode fiber

2,000m (6,560 ft)

Single-mode fiber

3,000m (9,840 ft)

UTP (<5MHz)

800m (2,624 ft)

Entrance Facilities

The entrance facility contains the telecommunication service entrance to the building. This facility may also contain campus-wide backbone connections. It also contains the network demarcation point, which is the interconnection to the local exchange carrier's telecommunication facilities. The demarcation point is typically 12 inches from where the carrier's facilities enter the building, but the carrier may designate otherwise.

What three cables are recognized in the structured 568 cabling standards?

Horizontal cables recognized by the ANSI/TIA-568-C standard are limited to the following: Four-pair, 100 ohm, unshielded or shielded twisted-pair cabling: Category 5e, Category 6 or Category 6A (ANSI/TIA-568-C.

What is the TIA 568 standard?

TIA/EIA-568 is a set of telecommunications standards from the Telecommunications Industry Association. This Standard contains requirements that facilitate the planning and installation of a structured cabling system in a commercial building environment.

What are the 3 categories of structured cabling standards?

Structured cabling components include twisted pair and optical cabling, patch panels and patch cables.

What are the two types of cables defined by TIA EIA?

The standard defines the use of fiber-optic cable (single and multimode), STP (shielded twisted pair) cable, and UTP (unshielded twisted pair) cable.